2011 Volume 67 Issue 6 Pages II_339-II_349
In this study, the reduction effect of the heat inflow on the rooftop and the indoor thermal environment was measured by using the elementary school building, the rooftop of the bilding was covered with the water contain concrete boards. And, conserve energy effect and effectiveness for the indoor thermal environment improvement were evaluated. The effect of the decrease of the surface temperature and the slab side temperature at water contain concrete boad plot remarkably from the measurement result during the July-September of 2010, the temperatures decrease 22°C at the surface, 15°C at the waterproof layer surface that was caused compared with the gravel covered roof. The water contain concrete boards plot always drove the ceiling side temperature and the indoor temperature low as a result of comparing with the indoor condition of the control plot. The temperature fluctuate was small at time that opened the window and ventilated, and ventilation was discontinued, it became big temperatures fluctuate. The effect of the decrease of 0.5°C in PMV and 0.5 in WBGT was caused while the room had sealed up, and the effect of the decrease of 0.3 in WBGT was caused while the ventilated state.