1997 年 62 巻 498 号 p. 57-63
On the basis of the results of the temperature measurements made in a full-scale test room, a simplified prediction model for simulating room air flow patterns in the underfloor air distribution system was developed, consisting of two vertical areas and three horizontal zones. The model and some derived relationships regarding air flow and heat reproduced the measured temperature profiles with practical accuracy. It was shown by comparison with the uniform room air temperature case, that the underfloor system consumes less energy and allows a lower temperature rise with an increase in heat load.