日本建築学会環境系論文集
Online ISSN : 1881-817X
Print ISSN : 1348-0685
ISSN-L : 1348-0685
超高層集合住宅におけるポンプ直送給水方式の稼動実態に関する研究
坂本 和彦村川 三郎高田 宏
著者情報
ジャーナル フリー

2012 年 77 巻 680 号 p. 771-777

詳細
抄録

The authors carried out measurements about the volume of water supply loads and the consumed amount of electric power by booster pump system in a super high-rise apartment house. On the basis of the results of measurements, the trend of fluctuation of water consumption and electric power were analyzed.
As for the estimation of suitable water supply loads, the authors applied the Monte Carlo simulation technique. In comparison with the results of simulation and the measurement data, the authors clarified that it was possible to estimate the volume of water supply loads by using the simulation method and suitable parameters.
As a result, the authors showed that it was possible to hold down the increase of the consumption of electric energy by using the suitable water supply system on the basis of the high accuracy for water supply demands estimation.

著者関連情報
© 2012 日本建築学会