大学研究施設に導入したリン酸型燃料電池コージェネレーションシステムの性能評価
佐藤 久明浅野 良晴岩井 一博
著者情報
ジャーナル フリー

2017 年 23 巻 54 号 p. 553-556

詳細
抄録

It is important to effectively utilize the waste heat from the electric generator in order to achieve high overall energy efficiency of cogeneration system (CGS). To examine the energy conservation efficiency of CGS on the actual situation, we have researched the operative situation of the PAFC-CGS that has been installed in the new building in the university. As a result, the primary energy consumption of the building was found to be 52.8% less compared to the benchmarks of DECC. And the annual average of the thermal efficiency of the PAFC-CGS was found to be 0.54.