中間階および基礎における免震レトロフィット工事 : 中間階免震対応設備・外壁
田中 収司森 正人大喜多 一晃杉崎 良一小山 実福井 克郎
著者情報
ジャーナル フリー

1997 年 3 巻 5 号 p. 23-26

詳細
抄録

Mid-story seismic isolation method was adopted to a 16 storied SRC building whose seismic resistance capacity turned out to be very poor. The building is the training center of Taisei corporation which was built in 1964. On the eighth floor, columns were cut apart to install isolators. In addition, the vertical shafts like equipment piping, elevator and staircase was slitted horizontally as well as the interior and exterior walls. In case of great earthquakes, maximum 18cm horizontal relative displacement occurs on the isolation floor. Vertical shafts and walls should follow such amount of relative displacement. In this report actual details and performances are described on each system.