This paper reports results of magnetic field measurements around power distribution equipment i.e. pad-mounted transformers, pad-mounted switchgears and vertical cables. Measurements were carried out in accordance with IEC 62110 which prescribes measurement and evaluation procedures of non-uniform as well as uniform magnetic fields generated by ac power systems with regard to public exposure. The average exposure level of magnetic field, corresponding to the spatial average over entire human body of magnetic field to which the individual is exposed, was evaluated for each power distribution equipment based on the measurement results. The maximum exposure level, the highest average exposure level over the area of interest, was also obtained. It was found that both exposure levels are much lower than the reference level from the ICNIRP Guidelines published in 2010.