This paper deals with harmonic voltage detection methods for a shunt active filter intended for installation on a power distribution system. The active filter acts as a resistor to damp out harmonic propagation throughout the power distribution system. However, the active filter may fall into an unstable condition, because the control system forms a complex feedback loop including harmonic detection, current control, and system impedance. Stability and harmonic-damping performance of two different harmonic detection methods, that are comprehensive harmonic detection and specific harmonic detection, are compared with each other. Moreover, a new compensation scheme for the comprehensive harmonic detection method is proposed to improve system stability.