IEEJ Transactions on Industry Applications
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
Paper
Discussions and Comparisons between Comprehensive Harmonic Detection and Specific Harmonic Detection in a Shunt Active Filter for Installation on a Power Distribution System
Hiroshi YamashitaJintakosonwit PichaiHideaki FujitaHirofumi AkagiJunya Shinohara
Author information
JOURNAL FREE ACCESS

2004 Volume 124 Issue 6 Pages 622-629

Details
Abstract

This paper deals with harmonic voltage detection methods for a shunt active filter intended for installation on a power distribution system. The active filter acts as a resistor to damp out harmonic propagation throughout the power distribution system. However, the active filter may fall into an unstable condition, because the control system forms a complex feedback loop including harmonic detection, current control, and system impedance. Stability and harmonic-damping performance of two different harmonic detection methods, that are comprehensive harmonic detection and specific harmonic detection, are compared with each other. Moreover, a new compensation scheme for the comprehensive harmonic detection method is proposed to improve system stability.

Content from these authors
© 2004 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback