IEEJ Transactions on Industry Applications
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
Special Issue Paper
A 6.6-kV Transformerless Cascade PWM STATCOM
—Experimental Verification by a Three-phase 200-V, 10-kVA Laboratory System—
Tsurugi YoshiiShigenori InoueHirofumi Akagi
Author information
JOURNAL FREE ACCESS

2007 Volume 127 Issue 8 Pages 781-788

Details
Abstract

This paper deals with a 6.6-kV transformerless STATCOM cascading multiple single-phase H-bridge PWM converters in each phase. The ac voltage of the STATCOM is almost sinusoidal, so that it requires no harmonic filter. Each converter is equipped with a capacitor and a voltage sensor on the dc side, which are electrically isolated from each other. The STATCOM has the capability of self-starting and voltage-balancing without any external power supply or equipment. Experiment by a three-phase 200-V, 10-kVA laboratry system, along with computer simulation, is carried out to confirm the viability and effectiveness of the STATCOM.

Content from these authors
© 2007 by the Institute of Electrical Engineers of Japan
Next article
feedback
Top