直列形電圧補償装置のデッドタイム電圧とインピーダンス電圧の抑制法
中田 篤史野嵜 正浩鳥井 昭宏植田 明照
著者情報
ジャーナル フリー

2011 年 131 巻 10 号 p. 1225-1231

詳細
抄録

Many research groups are developing series voltage compensators. In the series converter, since a transformer is used in series in the power system, the power system current flows into the voltage source inverter through the transformer. The inverter current, which is determined by the transformation ratio, gives rise to an error voltage that consists of a dead-time voltage and an impedance voltage; the error voltage is generated even when the reference voltage is zero. This paper describes the generation mechanism of the error voltage and proposes a method for reducing the error voltage.