2013 Volume 133 Issue 9 Pages 936-942
This paper provides an intensive discussion on the low-voltage-ride-through (LVRT) capability and performance of a phase-shifted PWM STATCOM using the modular multilevel cascade converter based on single-star bridge-cells (MMCC-SSBC). It follows the previous paper having focused on current control performance. This paper describes modeling, analysis, and design of the STATCOM, paying attention to the cluster-balancing control of the dc capacitor voltages. Experimental verification with a three-phase 150-V, 10-kVA downscaled model confirms that the STATCOM provides satisfactory LVRT capability against single-, double- and triple-phase voltage sags, and even against the most severe voltage sags with a voltage depth of 100%.
The transactions of the Institute of Electrical Engineers of Japan.C
The transactions of the Institute of Electrical Engineers of Japan.B
The transactions of the Institute of Electrical Engineers of Japan.A
The Journal of the Institute of Electrical Engineers of Japan