ホールICを用いた三相電流センサおよび零相電流センサ
原 和裕川守田 聰
著者情報
ジャーナル フリー

114 巻 (1994) 1 号 p. 51-56

詳細
PDFをダウンロード (1198K) 発行機関連絡先
抄録

Three-phase current sensors are required in power-line distribution systems to monitor currents and protect systems from possible failures. Zero-phase current sensors are also required to detect leakage currents between power lines and the earth, thus preventing accidents like a fire. This paper describes new three-phase and zero-phase current sensors which are based on a zero method. The sensors consist of Hall ICs, coils, and electronic circuits; no magnetic cores are used. The three-phase current sensor provides measurements of currents from 0.8 A to 720 A with excellent accuracy, while the zero-phase current sensor provides measurements from 90 mA to 20 A. The output signal levels are suitable for microprocessor-based metering and control systems. The sensors are relatively small and light-weighted compared to a conventional current transformer (CT). Moreover they withstand excess curents and do not yield burning or deterioration. They do not require expensive components so they have an advantage in cost compared to an optical-fiber current transformer.