An Evaluation of High Frequency Acceleration Test at XLPE Cable’s Insulator
Kimihiro IwasakiMasahiko NakadeAtsushi TanakaMihoko TanimotoMinoru OkashitaKazumi Ito
Author information
JOURNALS FREE ACCESS

2004 Volume 124 Issue 6 Pages 866-872

Details
Abstract

We investigated whether a high frequency acceleration method has validity at the degradation of XLPE in case of no influence of water for realizing a lifetime test at near the operating electric field. The tests was carried out at 50Hz, 1000Hz, and 3000Hz frequency using Recessed specimen and the specimen under Needle-plane electrode system, time-to-breakdown was measured. A clear property of frequency acceleration was checked in both results of tests, and the validity of the frequency acceleration technique was shown.
And we realize that frequency acceleration factor is lower than the frequency ratio at both tests of specimens. We think the reason is that the amount of accumulation of the space charge per cycle at a defect or a tree tip at high frequency is less than the accumulation at 50Hz. Moreover, tree growth time effects at the time to breakdown of Needle-plane system specimen, but it effects a little at Recessed specimen, so there is difference of acceleration rate between both specimens.
The lifetime exponent of V-t characteristic, n, increases at a 3000Hz examination, so it is suggested that n has a frequency dependence.