IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
DC Interruption Characteristic on Vacuum Circuit Breaker
Hiromi OdakaMasataka YamadaRyohei SakumaCuie DingEiji KanekoSatoru Yanabu
Author information
JOURNAL FREE ACCESS

2005 Volume 125 Issue 7 Pages 687-694

Details
Abstract

A high speed vacuum circuit breaker (HSVCB) has been investigated. HSVCB makes high frequency current superimposed on a fault current so that the current is forced to be zero and is interrupted. Its interruption performance is considered to be dependent on a rate of change of the current (di/dt). As a fundamental research, we investigated the di/dt-dv/dt characteristics and the insulation recovery characteristic after interrupting the counter-pulse current for various contact materials of AgWC, CuW, and CuCr. The results revealed that the case where gap length is larger is better in a current interruption performance. Moreover, it was found that di/dt is not dependent on the insulation recovery characteristics, but the magnitude of interruption current influences greatly.

Content from these authors
© 2005 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top