2012 Volume 132 Issue 11 Pages 922-927
The authors evaluate the sparkover rate of a medium-voltage line associated with direct strokes to the line by using peak currents obtained at southern Kyusyu by the JLDN (Japan Lightning Detection Network). In the evaluation, the correlation between the front duration and the peak currents is taken into account as well as the low-voltage line often installed below. As the result, the estimated sparkover rate for a flash is in reasonable agreement with the reported rate.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan