Influence of Numerous Current Interruptions on V-t Characteristics of a Vacuum Interrupter
Takaaki FurukawaAkiko KumadaShigeyasu MatsuokaHisatoshi IkedaKunihiko HidakaTetsu ShioiriJunichi Ikeda
Author information
JOURNALS RESTRICTED ACCESS

2013 Volume 133 Issue 9 Pages 725-726

Details
Abstract

The insulation strength of a vacuum interrupter is investigated before and after dozens of large current interruptions. The breakdown voltage decreases from 119.5kV to 103.2kV by the current interruption test.

Information related to the author
© 2013 by the Institute of Electrical Engineers of Japan
Previous article Next article