IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Construction of IEC 61850 System as Benchmark and Improving Method of GOOSE Reliability
Toru AmauYasutaka SakaKouichi NishiwakiYuichi SaikiTetsuo OtaniMutsumi AokiHiroyuki Ukai
Author information
JOURNAL FREE ACCESS

2014 Volume 134 Issue 9 Pages 783-790

Details
Abstract

Overseas utilities have been employing Substation Automation Systems (SAS) based on IEC 61850 in which Generic Object-Oriented Substation Event (GOOSE) provides a fast mechanism of transferring event data such as transfer trip. The GOOSE messages are required to be reliable enough to maintain electric supply reliability, even though off-the-shelf devices composing SAS have their fixed configurations about GOOSE. This paper proposes a method to improve reliability of GOOSE with redundant dispatchers and message retransmissions that can use the fixed configurations as is. It also describes experimental results using a test system dispatching GOOSE messages of transfer trip, and shows the advantage of our proposal.