2018 Volume 138 Issue 1 Pages 23-29
This paper describes rising and reducing processes of receiving-end voltage due to a reverse power flow from large photovoltaic generation in distribution electric power system. The dependences of the voltage increase and decrease on the length of distribution line are discussed with consideration of vector (phasor) diagram of voltage and current. Furthermore, the effect of leading power factor control of the PV system on the distribution line voltage is also quantitatively revealed.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan