2020 Volume 140 Issue 6 Pages 548-549
Surface charge accumulation phenomena on insulating epoxy spacer are measured under DC-GIS simulated environment. Homo-charges are accumulated near the electrodes, and charge injection from the electrodes is assumed to be dominant in surface charge accumulation. The surface charge is saturated at a time constant of 1000 hours below 20°C, and the saturated charge amount tends to increase with room temperature rising.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan