電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
論文
TDR測定時における配電設備の反射特性の定量評価
上嶋 宏明松嶋 徹久門 尚史和田 修己
著者情報
ジャーナル 認証あり

2022 年 142 巻 2 号 p. 139-149

詳細
抄録

The authors propose an effective method of fault location utilizing TDR measurement in overhead distribution systems. Past studies have shown that reflected waves from accident points such as short circuits, ground faults, and disconnections can be observed in overhead distribution systems. In addition, it is known that the retaining insulators and pulling insulators of overhead power distribution line cause reflected wave because these equipment act as capacitor. On the other hand, although there are many other distribution facilities, the reflection characteristics cannot be evaluated quantitatively. Based on the above, the purpose of this study is to create an equivalent circuit model for TDR measurement for various distribution facilities existing in the overhead distribution system. For modeling, an equivalent circuit model is created by the power system instantaneous value analysis program XTAP, and the experimental results and simulation results are compared and evaluated.

著者関連情報
© 2022 電気学会
前の記事 次の記事
feedback
Top