電気所構内の無線通信鉄塔への雷撃による低電圧回路への過電圧の発生と抑制対策の検証
吉田 昌展小椋 陽介伊佐治 宏子別所 克俊米澤 要清水 雅仁
著者情報
ジャーナル 認証あり

2024 年 144 巻 8 号 p. 461-469

詳細
抄録

In order to investigate measures to prevent damage to low-voltage circuits caused by direct lightning strikes to communication towers in electric supply stations, an impulse test was conducted and evaluated the effect of improving the grounding structure on reducing surge voltage in low-voltage circuits. The measures to improve the grounding structure include: (1) Reduction of the current itself flowing to the building ground wire. (2) Suppress the potential difference that occurs between the ground of the transformer for the power supply in the station and the building ground. (3) Eliminate the mixing of low-voltage cables with metal shielding (grounding at both ends of the shielding layer) and low-voltage cables without metal shielding. As a result of the experimental verification, we have confirmed that each of the three methods is effective in reducing the surge voltage generated in low-voltage circuits.