2025 Volume 145 Issue 6 Pages 434-442
Stator windings of hydro generators are exposed to combined thermal, voltage, environmental, and mechanical stresses, which deteriorate the insulation performance. On the other hand, various stator faults occur in the stator. The stator faults are accompanied by partial discharges, which may lead to dielectric breakdown depending on the type of faults. This paper presents a case study of detecting stator faults by on-line partial-discharge diagnostics. The type of stator faults is identified based on reproducible experiments. Furthermore, the advantages of online partial-discharge diagnostics compared with offline diagnostic methods in detecting stator windings are discussed.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan