IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Development of Partial Discharge Measurement Method for Pre-mold cable accessories with Separated Shielding Layers
Youichi NakataniMikio AdachiToshihiro MiyazakiTakashi Noma
Author information
JOURNAL FREE ACCESS

1995 Volume 115 Issue 10 Pages 1228-1233

Details
Abstract
Most of the accidents of XLPE cable line are caused by defective constructions of cable accessories. So we developed a method to measure paratial discharges in pre-mold cable accessories. We provided separared shielding layers as detection electorodes in accessories, and discriminate between paratial discharge pulse and noise pulse using realtime comparation of pulse current magnitudes from both de-tection electrodes.
This paper describe the principle of noise discrimination method, portabale paratial discharge mea-surement apparatus, and the result of field test.
Content from these authors
© The Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top