1998 Volume 118 Issue 11 Pages 1243-1248
Partial Discharge (PD) within voids in solid insulating system is a symptom and/or a direct cause of a deterioration of stator windings of a turbine generator. The bandwidth of the electromagnetic waves emitted from PD is very broad and ranges to GHz. We developed a new system based on “Spatial Phase Difference Method” for detecting microwave (GHz) emitted from PD. In this paper we applied this system to two off-line turbine generators in the overhaul and an on-line turbine generator which has two built-in antennas. On-line PD detection of the turbine generator is very useful for recognizing abnormal and/or deteriorated stator winding insulation without a machine outage. It was found that the detection system was able to detect microwave emitted from PD in operating turbine generator.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan