電気設備学会誌
Online ISSN : 2188-6946
Print ISSN : 0910-0350
ISSN-L : 0910-0350
論文
高圧需要家への自動力率調整装置導入が配電系統へ与える効果の定量評価
小林 浩青木 睦鵜飼 裕之原 英喜坂井 洋志梶井 拓也中村 光一
著者情報
ジャーナル フリー

2008 年 28 巻 2 号 p. 153-158

詳細
抄録

In some distribution lines,the voltage around the end of distribution line rises more than the regulation voltage. One of the reasons is the Ferranti effect caused by excessive amount of static capacity (SC) in high voltage (HV) consumers. In order to adjust the amount of SC, it is desirable to install the automatic power factor controller (APFC). However the APFC is not actually widespread, because its merit is not necessarily validated. In order to increase ratio of HV consumers installing the APFC, it is important to clarify merits of the APFC quantitatively. In the paper, from the result of measuring power factor etc.at receiving points in various HV consumers, the actual evaluation model of HV consumer is proposed. By using this model, the effectiveness of APFC is evaluated quantitatively. As the result, the reduction of electrical loss becomes about 2.0% of the whole electric energy in the feeder on the conventional distribution line.

著者関連情報
© 2008 一般社団法人 電気設備学会
前の記事 次の記事
feedback