Industrial Health
Online ISSN : 1880-8026
Print ISSN : 0019-8366
ISSN-L : 0019-8366
Noise Levels in a Hospital
Massimo BOVENZIAndrea COLLARETA
Author information
JOURNAL FREE ACCESS

1984 Volume 22 Issue 2 Pages 75-82

Details
Abstract

Noise measurements were performed in eight patients' rooms, three intensive care units (ICUs) and one operating theatre at a large hospital (1300 beds). Daytime and nighttime LAeq in patients' rooms and in ICUs were higher than the recommended standards. The measured noise levels could interfere with normal sleep and could be dangerous for patients at greatest risk. The laminar flow ventilation system was the main source of noise in the operating room. The LAeq recorded during a surgical procedure was sufficiently high to mask speech communication.
The measurement of A-weighted sound pressure levels disclosed that staff activities were responsible for the loudest noises. Air-conditioning systems and electro-mechanical instruments were also important contributors to noise pollution in the hospital.

Content from these authors
© National Institute of Occupational Safety and Health
Previous article Next article
feedback
Top