2023 年 43 巻 p. 19-27
This study proposes a new warm standby method for computer servers based on seismic response. The proposed method triggers a warm standby in the case that the exceedance probability of the safety limit of seismic response predicted by the last two-second observation record exceeds a preset threshold. Numerical simulations showed that the proposed method reduced the loss cost by 1.64% compared to conventional methods. To validate this method, we conducted shaking table tests. When a simulated earthquake motion was input, the loss cost was reduced by 60.6%. However, when observed records were input, the loss cost was increased by 3.89%. The results suggest that it is necessary improve the input ground motion model.