Decline of the performance of a portable axial-flow fan due to the friction and duct bending loss of a connected flexible duct
Jun Ojima
Author information
JOURNAL FREE ACCESS FULL-TEXT HTML

2017 Volume 59 Issue 2 Pages 210-213

Details
Abstract

Objectives: In a job site, a portable fan is often used to ventilate a confined space. When a portable fan is applied to such a space, the actual ventilation flow rate must be accurately estimated in advance because the safety level of contaminant and oxygen concentrations in the space will determine the ventilation requirements. When a portable fan is used with a flexible duct, the actual flow rate of the fan decreases due to the friction and duct bending loss of the duct. Intending to show the decline of a fan performance, the author conducted laboratory experiments and reported the quantitative effect of the friction and duct bending loss of a flexible duct to the flow rate of a portable fan. Methods: Four commercial portable fans of different specifications were procured for the experiments, and the decline of the performance of each portable fan due to the friction loss etc. of a connected flexible duct was investigated by measuring actual flow rate. Results: The flow rate showed an obvious decrease from the rated flow rate when a flexible duct was connected. Connection of a straight polyester flexible duct and a straight aluminum flexible duct reduced the flow rates to 81.2 - 52.9% and less than 50%, respectively. The flow rate decreased with an increase of the bend angle of the flexible duct. Conclusion: It is recommended that flow rate check of a portable fan should be diligently carried out in every job site.

Content from these authors

This article cannot obtain the latest cited-by information.

2017 by the Japan Society for Occupational Health
Previous article Next article
feedback
Top