In recent years, increasing electricity demand due to abnormal weather and the aging of thermal power generators have made it difficult to meet peak demand. As a solution, energy shifting using hydrogen to level annual demand has gained attention. This paper proposes a long-term operational planning method using a hydrogen energy storage system (HESS) for a large-scale system model covering the Hokuriku area. Annual demand trends were leveled based on historical demand data and output of the HESS was determined accordingly. By subsequently optimizing the start–stop schedules of thermal power plants, the demand fluctuation range was reduced from 3,350 MW to 2,874 MW. This resulted in the elimination of two thermal power plants and achieved annual cost savings of 2.062 billion yen. Although the introduction cost of the HESS remains high, this method demonstrates the potential to reduce the rated capacity of thermal power plants, suggesting that it could be an effective strategy for achieving a future carbon-neutral society.