The Proceedings of the Symposium on Environmental Engineering
Online ISSN : 2424-2969
2001.11
Session ID : 433
Conference information
Performance Evaluation of CO_2 Heat Pump Water Heater for Cold Area
Osamu KUWABARAHiroshi MUKAIYAMAToshikazu ISHIHARAToshiyuki EBARAHirokazu IZAKISakan INABAEiji SAKATANINaoki MORISHITA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
It is expected that CO_2 heat pump water heater performs enough heating capacity and high efficiency even in cold area. For the performance evaluation of this system, a test unit was operated in winter, in the open air. The heating capacity reached 4.5[kW], that was our target for residential use, at -20[℃] of ambient temperature. Annual average COP calculated on the weather data in Sapporo showed that CO_2 heat pump water heater was better than other heating systems in TEWI evaluation.
Content from these authors
© 2001 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top