Influence on Smoke Shield Performance which the Difference of the Air Supply Systems Causes in Pressurized Smoke Control -Relations with the Performance of Smoke Shield and Orthogonality Ingredient of the Wind Velocity and Static Pressure under the Dynamic Pressure Existence by Aeration Experiment at the Normal Temperature Using Full-scale Model-
Masashi KISHIUEJun-ichi YAMAGUCHISeiji OKINAGAKen MATSUYAMATakayuki MATSUSHITA
Author information
JOURNAL FREE ACCESS

2017 Volume 67 Issue 1 Pages 39-48

Details
Abstract

For the purpose of elucidating the influence that the difference in aeration method gave in smoke shield performance, an aeration experiment at the normal temperature was carried out using a full-scale model like the fire experiment. By the experiment, static pressure differences between aeration room and outside and The wind velocity of the ingredient vertical for the upper surface and the perpendicular surface in the smoke shield opening were measured. As a result, the following things were shown.
1) Non-dimensional static pressure difference P* is almost proportion to smoke shield performance.
2) Upper aspect non-dimensional wind velocity ratio Vu* is almost proportion to smoke shield performance.
3) The achievement of smoke shield requires the thrust from the perpendicular surface and the upper surface which are orthogonally crossing.