Reduction of Energy Consumed by CO2 Heat Pump for Raw Milk Cooling System
Mitsuyoshi ISHIDA Ryo NAKAKUBOMasahisa OOTAKEToshizou FUJIIHiroshi MUKAIYAMAKazuhisa NONAKAAtsuo IKEGUCHISanki HASEGAWA
Author information
JOURNAL OPEN ACCESS

2012 Volume 42 Issue 4 Pages 178-187

Details
Abstract
A pre-cooling system for raw milk was developed using a heat pump and an ice builder that employs a natural refrigerant, i.e., CO2; in addition, tests were conducted to evaluate the energy balance, thermal effi ciency, and other performance parameters of the system. The developed system recovers the waste heat, generated by the formation of ice in the ice builder, in the form of hot water (around 85°C). The hot water can be utilized to wash bulk cooler tanks and milk pipelines. The system was installed by two farmers in Tochigi prefecture. It had a heat exchanger effectiveness of approximately 45-79 %, and its deployment resulted in an annual reduction in energy consumption, running cost, and CO2 exhaust tonnage of approximately 34-49 %, 19-39 % (90 000-140 000 Yen), and 21-40 %, respectively.