主催: 公益社団法人 空気調和・衛生工学会
会議名: 令和2年度空気調和・衛生工学会大会(オンライン)
開催地: オンライン
開催日: 2020/09/09 - 2020/09/30
In this report, the results of experiments on the dew condensation limit of the double layer metal duct. Due to the air leak, the location where dew condensation occurs was different. In addition, the dew point temperature of the flange was lower than that of the duct surface. For the evaluation when introduce the actual building, the diagram of dew condensation limit created from the thermal network was used. As a result, dew condensation did not occur on the duct surface.