日本原子力学会和文論文誌
Online ISSN : 2186-2931
Print ISSN : 1347-2879
ISSN-L : 1347-2879
論文
全交流電源喪失時の使用済燃料ピット水温と水位の予測
柳 千裕村瀬 道雄吉田 至孝楠木 貴世志
著者情報
ジャーナル フリー

2012 年 11 巻 3 号 p. 193-202

詳細
抄録

  A prediction method for water temperature in a spent fuel pit of a PWR has been developed to calculate the increase in water temperature during the shutdown of cooling systems. In this study, the prediction method was extended to calculate the water level in a spent fuel pit during loss of all AC powers, and predicted results were compared with data of spent fuel pools in the Fukushima Daiichi Nuclear Power Station. The calculations gave reasonable results, but overestimated the decreasing rate of the water level and water temperature. This result indicated that decay heat was overestimated and evaporation heat transfer from the water surface was underestimated. Results of calculations with 80% decay heat and 155% (No. 4 pool) or 230% (No. 2 pool) evaporation heat flux were in good agreement with data. The data-fitted evaporation heat fluxes agreed rather well with the evaporation heat transfer correlation proposed by Fujii et al.

著者関連情報
© 2012 一般社団法人 日本原子力学会
前の記事 次の記事
feedback
Top