収着剤ロータを用いた複合式湿度調節システムの除湿性能
堀部 明彦高木 貞男稲葉 英男春木 直人
著者情報
ジャーナル フリー

2008 年 25 巻 4 号 p. 315-324

詳細
抄録

Desiccant air-conditioning system is a promising technology because the exhaust heat can be effectively used in the future. We have reported the proposed system that combines a desiccant rotor with a vapor compression refrigerator. The confirmation experiment of stability and the performance was conducted with the experimental prototype. The result showed that it had the performance that was necessary for dehumidification driving in the summer and the humidification driving in the winter. In this report, we examined the influence on humidity controlling performance of the processing air temperature and humidity. As a result, we got high dehumidification efficiency and clarified the dehumidification characteristic in dehumidification driving in the summer. Dehumidification efficiency about 4.0 kg/kWh and COP of the system about 2.0 in summer driving mode were obtained.

著者関連情報
© 2008 公益社団法人 日本冷凍空調学会