固定床型デシカント換気空調機の開発
第1 報:各種吸着材を用いたデシカントユニットの性能評価
宮崎 隆彦秋澤 淳進藤 伸二神戸 正純高塚 威濱本 芳徳森 英夫
著者情報
ジャーナル フリー

2009 年 26 巻 4 号 p. 521-532

詳細
抄録

The study investigated fixed bed desiccant units for ventilation and air-conditioning. The system mainly dehumidifies the outdoor fresh air to be supplied to an air-conditioned room. Hence, the airconditioning load of the air-conditioner in the room can be mitigated. Several adsorbents were compared from the viewpoints of humidity ratio at the outlet of the desiccant unit, dehumidified quantity per unit volume, and dehumidified quantity per unit adsorbent mass. The performance of the desiccant unit was predicted by simulation which was validated by comparison with experiment. The results revealed the most suitable adsorbent to reduce the desiccant unit size. It was also found that the humidity ratio at the outlet of the desiccant unit could be lowered by shortening the dimensionless switching time.