In this paper,a static analysis of double effect adsorption refrigeration cycle utilizing condensation heat is discussed. Double effect adsorption refrigeration cycle consists of two cycles, High Temperature Cycle (HTC) which is driven from external heat sources, and Low Temperature Cycle (LTC) which is driven by condensation heat from HTC. Both of HTC and LTC are using silica gel and water as working pairs. The effect of heat source temperature on cycle performance was investigated in terms of coefficient of performance (COP) and specific cooling energy (SCE). Results showed that double effect cycle would produce higher COP than single effect cycle for driving temperature observed between 80-150°C with the same operating condition. However, the value of SCE is lower than single effect, despite that the SCE of double effect cycle is improved with heat source temperature higher than 100°C. Further, it was also observed that adsorbent mass ratio of HTC and LTC affected performance of chiller. When adsorbent mass ratio of HTC and LTC was unity, it was found that SCE and COP took the maximum.