Mサイクルを用いた建築一体型太陽エネルギー駆動冷房システムによる省エネルギー可能性の評価
宮崎 隆彦秋澤 淳二階 勲
著者情報
ジャーナル フリー

2011 年 28 巻 3 号 p. 269-277

詳細
抄録

The study proposed a solar chimney driven evaporative cooling system that can be integrated into the ceiling of a building. The aims of the study are to analyze the boundary conditions, such as a radiative cooling load and the inlet air conditions, on the cooling performance of the system, as well as to predict the energy saving potential of the system. The simulation results revealed that the system could cope with the radiative cooling load of 40W/m2 when the solar radiation on vertical surfaces was above 200W/m2.The cooling load of the existing air conditioner would be reduced by 11% on a summer representative day, if the system was attached to the perimeter zone of a south-facing office room.