論文
種々の流路における有機系収着剤ロータへの二重通風除湿
-第1 報:各流路の除湿特性-
堀部 明彦春木 直人仁科 裕貴宮内 裕 昭
著者情報
ジャーナル フリー

2012 年 29 巻 1 号 p. 119-130

詳細
抄録

In this paper, the desiccant rotor with double ventilation system is proposed in order to improve the sorption efficiency of the rotor. In this system, the processing air is dehumidified with the rotor. Next, the air becomes high relative humidity by cooling with an air cooler, and it is ventilated to the rotor again for dehumidification. This desiccant rotor with the organic sorbent has high adsorption ability at high relative humidity and can be recovered at low temperature. In this study, ventilation experiments of four types of air flow routes were investigated. In the experiment, temperature and absolute humidity of the air at the entrance and exit of each zone were measured. It is clarified that each route has own characteristics on dehumidification. As a result, it is found the most suitable route of the double ventilation dehumidification system.

著者関連情報
© 2012 公益社団法人 日本冷凍空調学会