通風ドアに用いるアレイ状の枝管消音器に関する研究(直線的に拡大する形状の枝管による減音特性の改善)
坂本 秀一石田 宗弘珍田 美月
著者情報
ジャーナル フリー

2017 年 83 巻 850 号 p. 16-00575

詳細
抄録

In this article, we examined several longitudinal-sectional sizes of a silencer whose volume was limited by the thickness and aperture ratio of the ventilation door. We report the results of improvement in the sound attenuation properties of these shapes. As an evaluation method for the silencer, we measured transmission losses using an impedance measurement tube and calculated them on the basis of a theoretical analysis. The following results were obtained from the evaluation of the silencer using the measurement and calculation results and from the verification of the improved shape of a silencer and silencer array. For a side branch tube silencer with a 1/3 aperture ratio, assuming that it is installed into the ventilation door, we observed a side branch tube with an linear expanded longitudinal-sectional shape by improving the shape using the theoretical analysis of transmission losses. In addition, as a result of the experiment with a sample on the basis of the theoretical analysis, both the experimental and the theoretical analysis were in good agreement. Furthermore, the expanded shape of the longitudinal-section of the side branch tube decreased the frequency of the sound attenuation peak. It was found that a silencer with a combination of four of these silencers can be arrayed side-by-side in a ventilation door; this results in a flat transmission loss of more than 5 dB over a broad band.