BULLETIN OF THE GEOLOGICAL SURVEY OF JAPAN
Online ISSN : 2186-490X
Print ISSN : 1346-4272
ISSN-L : 1346-4272
Volume 60 , Issue 9-10
Special Issue: Study on geothermal heat pump application in tropical Asia
Showing 1-5 articles out of 5 articles from the selected issue
Preface
Article
  • Kasumi Yasukawa, Youhei Uchida, Norio Tenma, Yusaku Taguchi, Hirofumi ...
    2009 Volume 60 Issue 9-10 Pages 459-467
    Published: September 10, 2009
    Released: August 05, 2013
    JOURNALS FREE ACCESS
        In east Asia, where significant economical growth in this century is expected, intensive installation of geothermal heat pump (GHP) system may be important from both energy security and environmental protection aspects. Detailed underground temperature survey is essential for its promotion. Possibility of geothermal heat-pump application in tropical Asia is studied based on groundwater temperature data. Although generally geothermal heat-pump system may not have thermal merit for space cooling in tropics because subsurface temperature is generally higher than average atmospheric temperature, there may be some places in tropical regions where underground can be used as “cold heat-source”. In order to confirm this possibility, groundwater temperature surveys were widely conducted in the Chao-Phraya plain, Thailand and Red-river plain, Vietnam to compare with atmospheric temperature data. As a result, regional variation of subsurface temperature at depths from 20 to 50 m of 3.4 K was observed in the whole Chao-Phraya plain while that of 2.0 K was observed in the Red-river plain. In some cities, subsurface temperature lower than monthly mean maximum atmospheric temperature for 5 K or more over four months was identified. Thus underground may be used as cold heat-source even in parts of tropical regions.
    Download PDF (1533K)
  • Youhei Uchida, Kasumi Yasukawa, Norio Tenma, Yusaku Taguchi, Jittrakor ...
    2009 Volume 60 Issue 9-10 Pages 469-489
    Published: September 10, 2009
    Released: August 05, 2013
    JOURNALS FREE ACCESS
        Worldwide use of geothermal heat-pump (GHP) has extensively grown in recent two decades. Although generally geothermal heat-pump system may not have thermal merit for space cooling in tropics, there may be some places in tropical regions where subsurface can be used as “cold heat-source”. In order to confirm this possibility, subsurface temperature surveys were widely conducted in the ChaoPhraya plain, Thailand.
        As a result, the distribution of subsurface thermal gradients has marked differences between the lower and the upper plain. Thermal gradients in the upper plain are low, and most of them are below 1.0 oC/100 m. The thermal gradients in the lower plain, on the other hand, are generally high and show a tendency of lower gradient at peripheral areas and higher gradient at central parts (4.0 oC/100 m). This subsurface thermal regime is due to thermal conduction by regional groundwater flow system in the lower plain estimated by chemical compositions and stable isotope variations.
    Download PDF (2999K)
  • Kasumi Yasukawa, Isao Takashima, Youhei Uchida, Norio Tenma, Oranuj Lo ...
    2009 Volume 60 Issue 9-10 Pages 491-501
    Published: September 10, 2009
    Released: August 05, 2013
    JOURNALS FREE ACCESS
        An experimental geothermal heat pump system for space cooling was installed in Kamphaengphet, Thailand in 2006 and used for 17 months. Temeprature changes in the subsurface heat exchange tube and its surroundings were monitored to evaluate subsurface thermal properties and short- and long-term effects of operation of the system. Subsurface temperuatre increase due to the system operation recovered in few days and no long-term effect was observed after a year of operation. Room and atmospheric temperatures and electricity consumprion of the system were also measured through the period. Temperatures and flow rates of primary and secondary fluids were measured as well. As a result, a system COP (coefficient of performance) of around 3 was obtained for its stable operation period. The results of temperature measurements and calculation of system performances is presented in this paper.
    Download PDF (1966K)
  • Norio Tenma, Kasumi Yasukawa, Isao Takashima, Youhei Uchida, Oranuj Lo ...
    2009 Volume 60 Issue 9-10 Pages 503-509
    Published: September 10, 2009
    Released: August 05, 2013
    JOURNALS FREE ACCESS
        An experimental geothermal heat pump (GHP) system operation for space cooling was conducted in Kamphaengphet, Thailand from October, 2006 to March, 2008. Temperature sensors were installed in the heat exchange tube to monitor underground temperature for this test. Using this measured data, numerical simulation was performed in order to estimate subsurface thermal influence of the GHP system operation for space cooling. As the results of this calculation, the authors consider that the thermal influence of the GHP system operation at this test site is quite limited.
    Download PDF (1711K)