The authors deal with an initial stage of partial discharge inception phenomena at the triple junction formed in GIS. Partial discharge inception voltage (V
c) was measured by optical method during the application of positive lightning impulse voltage as parameters of the surface condition of electrode, and SF
6 gas pressure. As a result, the followings were obtained. (1) V
c is not affected by the surface condition of the electrode. It seems that initial electrons are supplied from negative ion, SF
6-, in the space charges formed by electron avalanche due to high field strength near the triple junction. (2) Covering the electrode with dielectric film is effective to the relaxation of the electric field near the triple junction. Therefore V
c for the dielectric coated electrode is higher than that for the bare electrode.