Several design factors of the period meter for nuclear reactors are analyzed. Using the results, a new transistorized period meter is developed.
Experimental data of this device are:
(1) Input signal level: 0.5V/decade
(2) Period range: -15+3sec
(3) Stability of period output for ambient temperature -10+60°C and AC line voltage 85115V: ±1%
(4) Drift of period output: ±0.1%/10hr
(5) Hysteresis of period scram level: ±0.1%
(6) Stability of period scram level for ambient temperature -10°C×60°C and AC line voltage 85115V: ±11%