The purpose of this study is to evaluate available fire demand that can be guaranteed in the small-scale block distribution system in the commercial area by analyzing the several types of the small-scale block model.
As a result, I came to the following conclusions.
(1) Even in case of small-scale blocks four hydrants can be guaranteed to open simultaneously at its maximum by 150 mm pipelines ,which is regulated by The Standard of Fire Demand , or by the standard condition that is under head loss of 5m.
(2) Five fire hydrants are guaranteed in the small-scale blocks, which have the scale of 5,000m
3/day or over, by the standard condition that is under head loss of 5m.