Quantity of
steam
consumed mainly by
steam
sterilizers were measured. Impurities in
steam
were also observed by installing
steam
sterilizers.1)
Steam
consumption in the central sterile supply department per day was 6% of
steam
for processes in the whole hospital. 25% of
steam
consumption in the central supply department was heat loss.
Steam
consumption marked the highest during the operating time of water sterilized-distillers amongst other equipment.
Steam
consumption by
steam
sterilizers marked the highest during a pre-heating time for a jacket. This value should be taken into consideration in designing a
steam
pipe line or bolier capacity. The hourly
steam
consumption was only one third of the highest other than that of the pre-heating time.2) Alkalinity (CaCO_3), hardness, SO_4^<3->, PO_4^<3->, and pH showed standard value. The degree of contaimination of the
steam
filter element was also observed 6th months after installation.The filter element was obviosuly contaminated by impurities in
steam
.
Steam
filters were quite effective in removing impurities in
steam
.3)Electron microscope and X-ray analysis proved to be more reliable than normal chemical analysis in analising elements of stains placed on the stainless steal bar by impurities in
steam
.