Performance Evaluation of the 2-Rotor Desiccant Cooling Driven with a Low Temperature Heat
Kosuke AndoAkio KodamaTsutomu HiroseMotonobu GotoHiroshi Okano
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Among the desiccant cooling process, two-rotor process consisting of a honeycomb rotor dehumidifier and a sensible heat exchanger is the mainstream of the cooling processes which are practically applied to supermarket, hospital and so on. Most of them are driven with a higher regeneration temperature around 100-140°C obtained from gas-engine heat pump or micro gas turbine generator. However, performance evaluation of the 2-rotor desiccant cooling regenerated by a low temperature heat around 50-80°C has not been carried out sufficiently considering the requirement of effective use of lower temperature waste heat. This study aims to clarify the influences of the operating condition, air conditions, and process configuration on the performance of the 2-rotor desiccant cooling.Effect of water spray evaporative cooling at the inlet of regeneration air stream on the process performance was also investigated. This evaporative cooling was expected to cause humidity increase in regeneration air reducing the dehumidifying performance of the honeycomb absorber, while the evaporative cooling plays an important role to produce lower temperature in supply air. Experimental results showed that the amount of dehumidified water at the process without water spray evaporative cooler was actually larger than that of process with water spray evaporative cooler. This behavior was due to increase of humidity or relative humidity in the regeneration air as expected. However, temperature of supply air produced by the process with evaporator was rather lower than that of the other, resulting higher COP value. It was concluded that the evaporative cooler effectively worked at higher regeneration temperature and lower ambient humidity.
Content from these authors
© 2004 The Society of Chemical Engineers, Japan
Previous article Next article
feedback
Top