Experimental study of the relationship between maximum common mode current and maximum magnetic field strength using a simple power distribution line model
Hiroyuki OkumuraTohlu MatsushimaNobuo KuwabaraTakeshi YamamotoToshiyuki WakisakaYuki Fukumoto
Author information
JOURNAL FREE ACCESS Advance online publication

Article ID: 2019XBL0004

Details
Abstract

The relation between maximum common mode current and maximum radiated magnetic field strength was experimentally studied using a simple power distribution line model. The common mode current was measured along the cable and the radiated magnetic field strength was measured around the model. They were evaluated using the S21 parameter. The frequency characteristic of both the maximum current and the maximum strength showed a closely similar pattern. Our evaluation of their correlation indicated that the relation between the maximum common mode current and the maximum radiated magnetic field strength could be represented by a straight line, and that 80% of the measured data was contained within 2dB of the regression line.