Abstract

The effect of adsorption temperature (20ºC; 25ºC) and switching time for adsorption and desorption processes of 60:60 min, 60:90 min, 60:120 min was experimentally investigated on adsorption dehumidification system. It was performed to examine the performance index and moisture adsorbed ability. We found that performance index and moisture adsorbed decreased with the increase of adsorption temperature. While the increase of switching time increases the moisture adsorbed. On the contrary, the performance index increased up to switching time 60:90 min and decreased afterwards. The highest performance index and moisture adsorbed were 0.75 and 900 g/h, respectively.