Evaluation and Application of Overvoltage into Communication Equipment Due to Potential Rise at Earthing Terminal of Distribution Line Induced by Lightning Surge
Katsuji ItoYasuo Hirose
Author information
JOURNAL FREE ACCESS

2008 Volume 128 Issue 9 Pages 1406-1415

Details
Abstract
Overvoltage induced by surge currents due to thunderstorm lightnings causes harmful breakdown troubles of CATV communication equipment installed in and with power distribution systems. In this paper, the origin and natures of surge currents, their invading route into the system, and the system components such as earth impedances affecting over voltages are studied. Transient analyses are then performed using an equivalent circuit to evaluate over voltages. Application of the obtained results to the field fault data of communication equipment and possible protection method of them are discussed.
Content from these authors
© 2008 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback