The Journal of the Institute of Electrical Installation Engineers of Japan
Online ISSN : 2188-6946
Print ISSN : 0910-0350
ISSN-L : 0910-0350
Study of correction method of measured earthing resistance of besement. - Part1. The case of hemispherical electrode. -
Hiroshi MoritaSaki UetaTakehiko Takahashi
Author information
JOURNAL FREE ACCESS

2011 Volume 31 Issue 2 Pages 150-155

Details
Abstract
The fall of potential method is generally used for measuring the earthling resistance. This method needs two auxiliary electrodes and it is required that two auxiliary electrodes are placed at enough distances from the earthling electrode,e. g. building foundation. However, in urban area there is not enough space for taking measurement. So,it is very difficult to measure the earth resistance precisely. However,there is the 4-potential method when it stand on the theory of the fall of potential method. It is purposed of this paper to basic study on correction method of measured earthling resistance by 4-potential method.
Content from these authors
© 2011 The Institute of Electrical Installation Engineers of Japan
Previous article Next article
feedback
Top