Numerical simulation is carried out for flow characteristics in a plenum fan and the influence of the diameter ratio of the rotating vaneless diffuser on the performance of plenum fan is analyzed. The diameter ratio of the rotating vaneless diffuser employed is from 1.03 to 1.3. The research results show that the rotating vaneless diffuser is able to enhance the performance of plenum fan. It is found that there is significant improvement in static pressure and efficiency at the diameter ratio of 1.05 at high flow coefficients, while the optimal diameter ratio is 1.2 at rated and low flow coefficient.